MGate MB3660-16-2DC

1,317.64

MGate MB3660 Series

Modbus gateway with dual LANs, dual DC power inputs, 16 RS-232/422/485 ports, 0 to 60°C operating temperature

Description

Modbus TCP Gateways

Whether wired or wireless, single or multiple serial ports, Moxa’s Modbus TCP gateway solutions connect Modbus RTU, DNP3, J1939, and PROFIBUS devices to Modbus TCP networks, making configuration, troubleshooting, and conversion quick and easy.

Ethernet Interface

  • 10/100BaseT(X) Ports (RJ45 connector)

    2 IP addresses
    Auto MDI/MDI-X connection

Ethernet Software Features

  • Industrial Protocols

    Modbus TCP Client (Master), Modbus TCP Server (Slave)

  • Configuration Options

    Web Console (HTTP/HTTPS), Device Search Utility (DSU), Telnet Console

  • Management

    ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, Telnet, UDP, NTP Client, RADIUS

  • MIB

    RFC1213, RFC1317

  • Time Management

    NTP Client

Serial Interface

  • Console Port

    RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)

  • No. of Ports

    16

  • Serial Standards

    RS-232/422/485 (software selectable)

  • Connector

    DB9 male

  • Baudrate

    50 bps to 921.6 kbps

  • Data Bits

    7, 8

  • Parity

    None, Even, Odd, Space, Mark

  • Stop Bits

    1,2

  • Flow Control

    RTS/CTS, DTR/DSR, RTS Toggle (RS-232 only)

  • RS-485 Data Direction Control

    ADDC® (automatic data direction control)

  • Pull High/Low Resistor for RS-485

    1 kilo-ohm, 150 kilo-ohms

  • Terminator for RS-485

    120 ohms

  • Isolation

    2 kV (I models)

Serial Signals

  • RS-232

    TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND

  • RS-422

    Tx+, Tx-, Rx+, Rx-, GND

  • RS-485-4w

    Tx+, Tx-, Rx+, Rx-, GND

  • RS-485-2w

    Data+, Data-, GND

Serial Software Features

  • Industrial Protocols

    Modbus RTU/ASCII Master, Modbus RTU/ASCII Slave

  • Configuration Options

    Serial Console

Modbus RTU/ASCII

  • Mode

    Master, Slave

  • Functions Supported

    1, 2, 3, 4, 5, 6, 15, 16, 23

  • Max. No. of Commands

    256 per serial port

  • Memory Size

    65535 bytes

Modbus TCP

  • Mode

    Client (Master), Server (Slave)

  • Max. No. of Client Connections

    256

  • Max. No. of Server Connections

    128

  • Functions Supported

    1, 2, 3, 4, 5, 6, 15, 16, 23

  • Max. No. of Commands

    256

  • Memory Size

    65535 bytes

Modbus (Transparent)

  • Max. No. of Client Connections

    256

  • Max. No. of Server Connections

    128

Power Parameters

  • Input Voltage

    Redundant dual inputs, 20 to 60 VAC (47 to 63 Hz)

  • No. of Power Inputs

    2

  • Power Connector

    Terminal block (for DC models)

  • Power Consumption

    390 mA @ 24 VDC

RelaysContact

  • Current Rating

    Resistive load: 2 A @ 30 VDC

Physical Characteristics

  • Housing

    Metal

  • Ip Rating

    Ip 30

  • Dimension (with ears)

    480 x 45 x 198 mm (18.90 x 1.77 x 7.80 in)

  • Dimension (without ears)

    440 x 45 x 198 mm (17.32 x 1.77 x 7.80 in)

  • Weight

    2780 g (6.13 lb)

Environmental Limits

  • Operating Temperature

    0 to 60°C (32 to 140°F)

  • Storage Temperature (package included)

    -40 to 85°C (-40 to 185°F)

  • Ambient Relative Humidity

    5 to 95% (non-condensing)

Standards and Certifications

  • Safety

    EN 60950-1, UL 60950-1

  • EMC

    EN 55032/24

  • EMI

    CISPR 32, FCC Part 15B Class A

  • EMS

    IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
    IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
    IEC 61000-4-4 EFT: Power: 1 kV; Signal: 1 kV
    IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
    IEC 61000-4-6 CS: 10 V
    IEC 61000-4-8 PFMF

  • Freefall

    IEC 60068-2-31

  • Shock

    IEC 60068-2-27

  • Vibration

    IEC 60068-2-6, IEC 60068-2-64

MTBF

  • Time

    482,835 hrs

  • Standards

    Telcordia SR332

Warranty